Focus: Fire-Life Safety / Column

Life Safety Q&A: Exiting from hospital into medical building

Brad Keyes discusses exiting from a hospital into a medical building

By Brad Keyes / Special to Healthcare Facilities Today


Q: A main circulation corridor in a hospital (Institutional Use I-2, 8' wide) passes thru the two-hour-use proup separation of adjacent medical offices (Business Use B) and re-enters the Institutional zone (two-hour wall) for egress to a fire egress stair. Building has automatic sprinkler system. Are egress corridor movements between Institutional and Business Use permitted? Must all sections of that corridor sequence maintain a consistent width of 8' clear?

A: [Boy… I wish you architects would use NFPA nomenclature instead of IBC… ☺]. If I understand your question correctly, my reply would be yes… you can exit from the hospital into a business occupancy, but there are extenuating circumstances. Section 6.1.14.1.2 of the 2012 LSC says when an exit access (i.e. corridor) from an occupancy traverses another occupancy, the multiple occupancy must be treated as a mixed occupancy. For you, that means the most restrictive occupancy requirements apply, which in your case would be healthcare occupancy.

So, this means everything required for healthcare occupancy must be met in the business occupancy building, such as:

  • Construction type

  • Fire alarm system

  • Sprinklers

  • Fire-dampers/smoke dampers

  • Corridor width

  • Corridor doors

  • Fire safety plans

  • Door latching and locking requirements

  • Etc.  

However, if you can call the two-hour fire barrier separating the healthcare occupancy from the business occupancy, a horizontal exit, then you would not have to meet the requirements of healthcare occupancy, in the business occupancy building.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



November 22, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

Building Around Care: Lessons in Modernizing Active Healthcare Environments

The challenge is how to modernize a healthcare facility while patients continue receiving care and physicians, nurses and staff continue providing it.


St. Luke's Heart Hospital Opens at Anderson Campus in Pennsylvania

The five-story, approximately 355,000-square-foot facility is seamlessly integrated into St. Luke's Anderson Campus.


WindRose Health Network Ensnared in Vendor Data Breach

The incident involved a previously undisclosed vulnerability in a remote-management tool that is used by one of its vendors.


How Efficiency Checklists Help Hospitals Save Energy, Water and Money

Keith Edgerton explains how a simple, systematic tool can help healthcare facilities identify savings, support sustainability goals and reinvest in long-term decarbonization.


Intermountain Healthcare Receives $50M Gift for Standalone Children's Hospital

To honor the family's gift, Intermountain Health will name the inpatient tower the Larry & Heidi Canarelli Inpatient Tower.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.