Focus: Fire-Life Safety / Column

Life Safety Q&A: Exiting from hospital into medical building

Brad Keyes discusses exiting from a hospital into a medical building

By Brad Keyes / Special to Healthcare Facilities Today


Q: A main circulation corridor in a hospital (Institutional Use I-2, 8' wide) passes thru the two-hour-use proup separation of adjacent medical offices (Business Use B) and re-enters the Institutional zone (two-hour wall) for egress to a fire egress stair. Building has automatic sprinkler system. Are egress corridor movements between Institutional and Business Use permitted? Must all sections of that corridor sequence maintain a consistent width of 8' clear?

A: [Boy… I wish you architects would use NFPA nomenclature instead of IBC… ☺]. If I understand your question correctly, my reply would be yes… you can exit from the hospital into a business occupancy, but there are extenuating circumstances. Section 6.1.14.1.2 of the 2012 LSC says when an exit access (i.e. corridor) from an occupancy traverses another occupancy, the multiple occupancy must be treated as a mixed occupancy. For you, that means the most restrictive occupancy requirements apply, which in your case would be healthcare occupancy.

So, this means everything required for healthcare occupancy must be met in the business occupancy building, such as:

  • Construction type

  • Fire alarm system

  • Sprinklers

  • Fire-dampers/smoke dampers

  • Corridor width

  • Corridor doors

  • Fire safety plans

  • Door latching and locking requirements

  • Etc.  

However, if you can call the two-hour fire barrier separating the healthcare occupancy from the business occupancy, a horizontal exit, then you would not have to meet the requirements of healthcare occupancy, in the business occupancy building.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



November 22, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

Disinfectant Contact Time: The Case for Biofilm Disruption

Contact time, while essential for compliance, does not reliably predict microbial reduction on actual healthcare surfaces.


Rethinking How Healthcare Facilities Fund Construction Projects

Rising costs and competing priorities are driving healthcare organizations to explore new financing arrangements and construction strategies.


Putting Trauma-Informed Design into Practice

Arnold's Place demonstrates how design choices can promote dignity and a sense of control for those experiencing homelessness.


Harris Health to Build New Freestanding Cancer Center

The center is planned to open in 2029, following the opening of the new O'Quinn Hospital along the North Loop at Lockwood.


Inland Empire Health Plan Opens Expanded San Bernardino Community Wellness Center

The new 33,000-square-foot center is nearly three times the size of the original location off Second Street.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.