Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: ILSM in business occupancies

Brad Keyes discusses regulations ILSM in business occupancies

By Brad Keyes / Special to Healthcare Facilities Today


Q: Is there a code requirement for implementing an Interim Life Safety Measure (ILSM) for occupancies other than healthcare (i.e. business occupancies) if a life safety code deficiency has been identified?

A: Yes… ILSM (also known as Alternative Life Safety Measures) is found in chapter 4 of the 2012 Life Safety Code, specifically section 4.6.10.1 of the 2012 LSC. This describes the need to implement ALSMs when features of Life Safety are impaired. This chapter is part of the ‘core’ chapters and applies to all occupancy chapters, so that means it applies to business occupancies as well.

Most accreditation organizations should be enforcing this in offsite locations, such as business occupancies. Some surveyors fail to ask for this, but it is an enforceable requirement.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



April 10, 2019


Topic Area: Regulations, Codes & Standards


Recent Posts

What 'Light' Daily Cleaning of Patient Rooms Misses

Most environmental services workers still clean as if they were wiping dust off a countertop, not disrupting a living, structured community.


Sprinkler Compliance: Navigating Code Mandates, Renovation Triggers and Patient Safety

As CMS deadlines approach and renovation projects accelerate, healthcare facility managers must understand how NFPA 101, state fire codes and sprinkler design strategies intersect.


MUSC Board of Trustees Approves $1.1B South Carolina Cancer Hospital

Research and education are intentionally embedded in the hospital’s design, with dedicated spaces for scientific collaboration, clinical investigation and training.


Study Outlines Hand Hygiene Guidelines for EVS Staff

Researchers find that current guidelines for hand hygiene don’t include EVS workers and suggest indicators to fill that gap.


McCarthy Completes $65M Sharp Rees-Stealy Kearny Mesa MOB Modernization

The completed tenant improvement includes approximately 100,000 square feet of improved space across two buildings and represents an investment of $65 million.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.