Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Start/Stop Times For Generator Load Test

Brad Keyes discusses regulations for generator load tests

By Brad Keyes / Special to Healthcare Facilities Today


Q: Is there a standard, that says we need to write the start and stop time on our monthly generator load test for 30 minutes?

A: In so many words there is. I agree that you won’t find a specific standard that says you must record the start and stop times of each test, but section 8.4.2 of NFPA 110-2010 says Diesel generator sets in service shall be exercised at least once monthly, for a minimum of 30 minutes, using one of the following methods:

(1) Loading that maintains the minimum exhaust gas temperatures as recommended by the manufacturer

(2) Under operating temperature conditions and at not less than 30 percent of the EPS nameplate kW rating

If you do not record the start and stop times then how do you prove to a surveyor that you tested the generator for 30-minutes?

It is reasonable and logical for a surveyor to expect you to record the start and stop times to ensure you tested the generator for 30 minutes.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



September 30, 2020


Topic Area: Regulations, Codes & Standards


Recent Posts

What 'Light' Daily Cleaning of Patient Rooms Misses

Most environmental services workers still clean as if they were wiping dust off a countertop, not disrupting a living, structured community.


Sprinkler Compliance: Navigating Code Mandates, Renovation Triggers and Patient Safety

As CMS deadlines approach and renovation projects accelerate, healthcare facility managers must understand how NFPA 101, state fire codes and sprinkler design strategies intersect.


MUSC Board of Trustees Approves $1.1B South Carolina Cancer Hospital

Research and education are intentionally embedded in the hospital’s design, with dedicated spaces for scientific collaboration, clinical investigation and training.


Study Outlines Hand Hygiene Guidelines for EVS Staff

Researchers find that current guidelines for hand hygiene don’t include EVS workers and suggest indicators to fill that gap.


McCarthy Completes $65M Sharp Rees-Stealy Kearny Mesa MOB Modernization

The completed tenant improvement includes approximately 100,000 square feet of improved space across two buildings and represents an investment of $65 million.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.