Q: In a hospital emergency department, can the corridors be six feet wide? Can the hospital install an 18-inch-deep lockable computer cabinet in the 8-foot ED corridor?

A: No… unfortunately you can’t. Most AHJs would allow this but one major AHJ will not.

If you claim the ER is a suite, then there would be no problem with a cabinet in the 8-foot wide hallway…. Because there are no corridors in a suite. What looks like a corridor in a suite is a communicating space and you would only have to maintain 36 inches of clearance for aisles.

But if the ER is not a suite, then you must maintain corridor widths. If you can classify the ER as an ambulatory healthcare occupancy, then the corridor width is 44 inches and placing a cabinet in the corridor would be permitted as long as you maintained 44 inches of clear width.  But I have been told by CMS that they will not allow an ER to be classified as an ambulatory healthcare occupancy because they believe ERs provide sleeping arrangements for patients under a 24-hour watch. Ugh. I find that hard to accept but I’m not the AHJ.

So, CMS would have you classify all ERs as healthcare occupancies which would then require a clear 8-foot-wide corridor because of the sleeping arrangements (if it was not a suite). I don’t agree with this interpretation by CMS. I would think you could say there are no inpatients in the ER but CMS doesn’t see it that way. You have to follow the most restrictive requirement and CMS’ interpretation is by far, the most restrictive interpretation.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



May 3, 2017


Topic Area: Safety


Recent Posts

What Does Light Daily Cleaning Miss in Patient Rooms?

Most environmental services workers still clean as if they are wiping dust off a countertop, not disrupting a living, structured community.


Smart Lighting Overhaul Boosts Efficiency, Diagnostics and Wellness at Bryan Health

Case study: LED upgrade and advanced controls across Bryan Health campuses cut lighting energy use by 57 percent while enhancing patient care and staff productivity.


AdventHealth Opens New Freestanding ER in Florida

The approximately 13,700-square-foot emergency room features 12 patient rooms, respiratory therapy services, diagnostic imaging including CT scans, X-ray and ultrasound.


Dirty Floors: How Pathogens Can Accumulate and Spread Underfoot

Studies show that healthcare floors are covered in bacteria and can quickly spread throughout patient rooms. 


WellSpan Health Opens Its Newberry Hospital in Pennsylvania

This marks the opening of its 10th hospital in the region spanning Central Pennsylvania and Northern Maryland.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.